Jackwell pressure transmitter

FD3051 Differential Pressure Level Transmitter


1 Application 
The differential pressure level transmitter 
is suitable to measure liquid, gas, or steam flow as 
well as liquid level, density and pressure. 
outputs a 4~20mADC signal corresponding to the 
measured differential pressure. Its highly accurat
and stable sensor can also measure the static 
pressure which can be shown on the integral 
indicator or remotely monitored via HART 
communications. Other key features include quick 
response, remote set-up using communications, self
diagnostics and optional status output for pressure 
high/low alarm. The range Limits is 0
The flange’s working pressure are 
1.6/4MPa,6.4MPa,10MPa,150psi,300psi or 600psi.
2 Operation Theory and Structure
FD3051LT differential pressure level transmitter is 
composed of a series differential pressure transmitter 
and the welding installation level flange. The 
operation theory is the same as 
differential pressure transmitter (consult 
series differential pressure transmitter general 
specifications), Only the high pressure side of 
pressure transmission path is different. The pressure 
Loaded in the high side, pass from the isolation 
diaphragm and silicone oil in the flange to the sensor.
3 Input 
Measured value: Differential pressure, Level
Measuring range 
Lower range value: -100% to +100% of the 
URL(continuously adjustable) 
Upper range value: Up to
URL(continuously adjustable) 
33
Transmitter
Differential Pressure Level 
The differential pressure level transmitter FD3051LT 
is suitable to measure liquid, gas, or steam flow as 
well as liquid level, density and pressure. FD3051LT 
outputs a 4~20mADC signal corresponding to the 
measured differential pressure. Its highly accurate 
and stable sensor can also measure the static 
pressure which can be shown on the integral 
indicator or remotely monitored via HART 
communications. Other key features include quick 
up using communications, selfl status output for pressure 
high/low alarm. The range Limits is 0—1kPa~2MPa, 
The flange’s working pressure are 
1.6/4MPa,6.4MPa,10MPa,150psi,300psi or 600psi.
Structure
differential pressure level transmitter is 
series differential pressure transmitter 
and the welding installation level flange. The 
operation theory is the same as FD3051 series 
differential pressure transmitter (consult FD3051 
series differential pressure transmitter general 
the high pressure side of 
pressure transmission path is different. The pressure 
Loaded in the high side, pass from the isolation 
diaphragm and silicone oil in the flange to the sensor.
Differential pressure, Level
100% to +100% of the 
100% of the 
Spans 
Table 1:Span code, measuring range and SWP
Span 
code 
Measuring range
Min Max
B 1kPa 6kPa
C 4kPa 40kPa
D 25kPa 250kPa
F 300kPa 3MPa
Table 2: Flange and minimum measuring range
Flange Nominal
diameter
Bulge sealing
DN 50/2”
DN 80/3”
DN 4”
Flat sealing 
DN 50/2”
DN 80/3”
DN 4”
The minimum measuring range of the differential 
pressure Level transmitter should
the minimum range of table 1 and table 2.The adjusted 
span must not be lower than the minimum
4 Output 
Output signal 
Two wire 4~20mADC output with digital 
communications, linear or square root programmable.
HART FSK protocol are superimposed on the 4~20 
mADC signal. Output range: 3.9 mA to 20.5 mA.
Failure Alarm (the mode can be selected) 
Low Mode (min): 3.7 mA, High Mode (max): 21 mA 
No Mode (hold): Keep the effective value before the 
fault. Note: The standard setting of failure alarm is High 
Mode. 
5 Response Time 
The amplifier damping constant is 0.1 sec; The sensor 
and flange’s damping constant is 0.2~3 sec, it depends 
on the range and range compression ratio. Amplifier
damping time constant is adjustable from 0.1 to 60 sec 
by software and added to response time. 
6 General conditions 
 Installation conditions 
The transmitter can be directly flanged in any position. 
Preferably in such a position that the process flange 
axes are vertical. Deviations from this can cause a shift 
in the zero, which can be corrected. The electronic
housing can be rotated through 360°and can be fixed 
in any position. A stop prevents the housing being 
turned too far. 
Ambient conditions 
Ambient temperature 
Min:depends on the fill 
fluid Max:85℃ 
-20~65℃,with LCD-indicator 
Storage temperature/transport temperature 
Min:depends on the fill fluid 
Max:85℃ Humidity:0~
100% 
Shock resistant: Acceleration:50g,Duration:11ms 
Vibration resistance: 500Hz on 2g 
Electromagnetic Compatibility (EMC) 
Look the EMC Performance Table 3 
Process conditions 
Temperature limits:-30~180℃ 
Pressure limits: From 3.5kPa abs. to working 
pressure. Proof pressure up to 1.5-times the nominal
pressure simultaneously on both sides of the 
transmitter admissible. 
Flange working pressure 
ANSI:150psi~600psi 
DIN: PN 1.6MPa~PN 10MPa 
One-sided overload: One-sided overload up to the 
rated pressure. Possibly occurring zero offsets can be 
corrected. 
Weight:DN 50/2”about 7~10kg;DN 80/3” about 8~ 
11kg;DN 4” about 9~12kg 
Explosion Protected Type 
NEPSI / ATEX: Ex dⅡC T6 
NEPSI / ATEX: Ex iaⅡC T4 
Amb. Temp.: -40℃~65℃ 
 Supply & Load Requirements 
24VDC supply, R≤(Us-12V)/Imax kΩ, Imax=23 mA. 
Maximum voltage limited: 42VDC, Minimum voltage 
limited: 12VDC, 15VDC(with LCD display) 
230Ω to 600Ω for digital communication 
Wetted Parts Materials 
Flange: 316 stainless steel 
Isolating Diaphragm:316L stainless steel / Hastelloy 
C/FEP or PFA plated on 
316L/Tantalum 
Nuts and Bolts: 304 stainless steel 
Process Connector: 316 stainless steel 
Fill fluid: Silicone oil/ Vegetable oil 
Process Connector Gasket:Perbunan(NBR)/Viton 
(FKM)/Teflon(PTFE) 
Amplifier Housing: Aluminum with epoxy resin coat 
Housing Gasket: Perbunan(NBR) 
Name plate and tag:304 stainless steel 
Degrees of Protection: IP67 
Electrical Connection 
The electrical connection is made via cable entry 
M20x1.5.The screw terminals are suitable for wire 
cross-sections up to 2.5mm2
Process Connection 
Flange with fixing thread 7/16-20 UNF and 1/4-18 NPT
female thread on both sides. The level flange comply 
with the ANSI standard or DIN standards. 
Table 3 : EMC Performance Table 
Items Test items Basic standards Test conditions 
Performance
Level 
1 Radiated interference (Housing) GB/T 9254-2008 30MHz~1000MHz OK 
Conducted interference(DC 
power port) 
GB/T 9254-2008 0.15MHz~30MHz OK 
Electrostatic Discharge (ESD) 
Immunity 
GB/T 17626.2-2006 
4kV(Line) 
8kV(Air) 
RF electromagnetic field 
immunity 
GB/T 17626.3-2006 10V/m (80MHz~1GHz) A 
Frequency magnetic field 
immunity 
GB/T 17626.8-2006 30A/m A 
Electrical Fast Transient Burst 
Immunity 
GB/T 17626.4-2008 2kV(5/50ns,5kHz) B 
7 Surge Immunity GB/T 17626.5-2008 
0.5kV(line to line) 
1kV(line to ground) 
(1.2us/50us) 
Conducted interference 
immunity induced by RF field 
GB/T 17626.6-2008 3V (150KHz~80MHz) A 
Note:(1)Performance level A description: The technical specifications within the limits of normal performance. 
(2)Performance level B description: Temporary reduction or loss of functionality or performance, it can restore 
itself. The actual operating conditions, storage, and data will not be changed