Part Number: YTA610-JA1C2DK/A/KU2
Model and Suffix Codes
- Model: YTA610 – Temperature Transmitter
- Output signal: -J – 4 to 20 mA DC with digital communication HART 7 protocol
- A: Always A
- Sensor input: 1 – Single
- Housing code: C – Stainless
- Electrical code: 2 – 1/2 NPT female
- Integral indicator: D – Digital Indicator with Local Operating Switch
- Mounting bracket: K – SUS316 stainless steel 2-inch vertical pipe mounting bracket
- Lightning protector: /A – Allowable current: Max. 6000A(8×20?s), repeating 1000A(8×20?s), 100 times
-
ATEX: /KU2
4-20 mA:
[Intrinsically safe approval]
Applicable Standard: EN 60079-0; 2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T5…T4 Ga
Ambient Temperature: -40 to 70?C for T4, -40 to 50?C for T5
Enclosure: IP66/IP67 in accordance with only IEC 60529
Entity Parameters:
Supply/Output circuit: Ui=30V, li=200mA, Pi=1.0W, Ci-22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10?F, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s., 1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
Certificate: KEMA 07ATEX0130
II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex IIIC T70?C/T90?C Db
Ambient Temperature for Gas Atmospheres: -40 to 75?C for T6, -40 to 80?C for T5
Ambient Temperature for Dust Atmospheres: -30 to 65?C for T70?C, -30 to 80?C for T90?C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female?
- Applicable for Electrical Connection Code 2 and 4.
- Estimated Lead Time: 8 – 10 Weeks
- Shipping Weight: 3 Kg