Fisher Positioners
Contact us
TEL: 001-646-569-9958
FAX: 001-646-569-9958
E-mail: services@myjackwell.com
Add:245 E MAIN ST STE 115,ALHAMBRA CA 91801,USA
Fisher Positioners
FISHER DVC2000 Digital Valve Controller/Positioner
Fisher (Fisher) DVC2000 intelligent electric valve positioner
More Models and low price, please contact services@myjackwell.com
Products: Fisher DVC2000 intelligent electric locator
Input signal: 4-20mA DC supply voltage: 5-30V DC
Maximum supply pressure: 7bar (101psi)
Recommended minimum supply pressure: the maximum ratio actuator big 0.5bar (7psi) mode of action: Single action positive action
Output pressure: Standard 1.3-3.3bar (20-49psi), optional 3.4-7.0bar (50-100psi)
Integration options: two independent hardware limit switch and valve position feedback (4-20mA DC output)
Communication protocol: In addition to supporting Hart, the optional support Wireless Hart, FOUNDATION, Profibus
Optional valve performance diagnostic capabilities: AD Advanced Diagnostics (Off-line off-line performance diagnostics),
PD Performance Diagnostics (On-Line line performance diagnostics)
Standard Electrical Interface: G1 / 4F Optional Electrical connection: 1/2 "NPTF
Standard air interfaces: M20X1.5 optional air connection: 1/4 "NPTF
Installation Standard: IEC 60534-6-1, IEC 60534-6-2, VDI / VDE 3845 and NAMUR
Explosion-proof grade: Ex ia IIC T4 / T5 intrinsically safe
Protection: IP66 Temperature: -40 ° C-85
Straight trip actuator stem travel Range Min: 6.35mm Max: 606mm
Row angular rotary actuators rotation angle available: Minimum angle: 45 ° Maximum angle: 90 ° C
Ordering Information (order information)
1. Actuator type and size (the actuator type and size)
1.1 Housing Style: GX Actuator and installed in GX three-way valve (mounted on the GX actuator)
1.2 Housing Style: Rotary & Sliding Stem (mounted on rotary actuators and other stroke actuators)
1.3 Are Built 4-20mA feedback and two-point level limit switch
2. Supply Pressure instrument air supply pressure
2.1 1.3 to 3.3bar (20 to 49psig)
2.2 3.4 to 7.0bar (50 to 100psig)
3 .Diagnostic Tier Lever (locator diagnostic rating)
3.1 HC Hart Communication (Hart Communication)
3.2 AD Advanced Diagnostics (Off-line off-line performance diagnostics)
3.3 PD Performance Diagnostics (On-Line line performance diagnostics)
4. Options (option)
4.1. Ingetrade 4-20mA Position Transmitter & (2) Limit Switches
(With integrated valve position transmitter and limit switch)