Part Number: YTA610-JA1A2DN/FU1/A/X2/C2/N4
Model: YTA610 Temperature Transmitter
Manufacturer: Yokogawa
Condition: New & Original in Factory Packing
Factory Warranty: 12 Months
Model and Suffix Codes
Model | YTA610 | YTA610 Temperature Transmitter |
Output signal | -J | 4 t0 20 mA DC with digital communication HART 7 protocol |
A | Always A | |
Sensor input | 1 | Single |
Housing code | A | Aluminum |
Electrical connection | 2 | 1/2 NPT female |
Integral indicator | D | Digital indicator with Local Operating Switch |
Mounting Bracket | N | None |
FM (US) | /FU1 |
4-20mA: [Intrinsically safe approval/non-incendive approval] Applicable standard: Class 3600:2011, Class 3610:2015, Class 3611:2004, Class 3810:2005, ANSI/ISA-60079:2013, ANSI/ISA-60079-11:2014, NEMA 250:2003, ANSI/IEC 60529:2004 (R2011) Intrinsically safe for Class I, II, III Division 1, Groups A, B, C, D, E, F, G, T5 … T4 Class I Zone 0 AEx ia IIC T5 … T4 Non-incendive for Class I, II, Division 2, Groups A, B, C, D, F, G, T5 … T4 Class III, Division 1 T5 … T4 Class I Zone 2 Group IIC T5 … T4 Ambient Temperature: -40 tp 70°C for T4, -40 to 50°C for T5 Enclosure Type 4X, IP66/IP67 in accordance with only IEC 60529 Entity Parameters: Intrinsically safe for Supply/Output circuit: Ui30V, li=200mA, Pi=0.1W, Ci=22nF, Li=0mH Sensor circuit: Uo=6V, lo=90=mA, Po=135mW, Co=10µF, Lo=3.9mH Non-incendive for Supply/Output circuit: Ui=30V, Ci=22nF, Li=0mH Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH Dielectric strength: 500 V a.c.r.m.s., 1 min [+, -, C, 1, 2, 3, 4, 5] to Earth terminal [+, -, C] to [1, 2, 3, 4, 5] [Explosionproof approval] Applicable standard: Class 3600, Class 3615, Class 3810, ANSI/NEMA250 Class I, Division 1, Groups A, B, C, D.; Class II/III, Division 1, Groups E, F and G. \’FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.\’ Enclosure Ratings: TYPE 4X Temperature Class: T6 Ambient Temperature: -40 to 60°C (-40 to 140°F) Electrical Connection: 1/2 NPT female(1) |
Lighting protector | /A | Allowable current: Max. 6000A (8×20µs), repeating 1000A (8×20µs). 100 times |
Painting(2) | /X2 | Coating change(3): High anti-corrosion coating |
NAMUR NE43 compliant(4) | /C2 |
Output signal limits: 3.8 mA to 20.5 mA
Failure alarm down-scale: output status at CPU failure and hardware error is -5%, 3.2 mA or less. |
Wired tag plate | /N4 | SUS316 stainless steel tag plate wired onto transmitter |
- Applicable for Electrical Connection Code 2.
- Not applicable for Stainless housing.
- Not applicable for color change.
- Not applicable for Fieldbus type.
- Estimated Lead Time: 8 – 10 Weeks
- Shipping Weight: 5 Kg