Home > Product > Pressure Transmitter > Yokogawa

Yokogawa

Contact us

TEL: 001-646-569-9958
FAX: 001-646-569-9958
Add:245 E MAIN ST STE 115,ALHAMBRA CA 91801,USA
> Read more

Yokogawa

YTA610-JA1A4DD/A/FU1 | Yokogawa YTA610 Temperature Transmitt

Part Number: YTA610-JA1A4DD/A/FU1

Model: YTA610 Temperature Transmitter
Manufacturer: Yokogawa
Condition: New & Original in Factory Packing
Factory Warranty: 12 Months
 

Model and Suffix Codes

Model YTA610 YTA610 Temperature Transmitter
Output signal -J 4 t0 20 mA DC with digital communication HART 7 protocol
  A Always A
Sensor input 1 Single
Housing code A Aluminum
Electrical connection 4 M20 female
Integral indicator D Digital indicator with Local Operating Switch
Mounting Bracket D SUS304 stainless steel 2-inch vertical pipe mounting bracket
Lighting protector /A Allowable current: Max. 6000A (8×20µs), repeating 1000A (8×20µs). 100 times
FM (US) /FU1 4-20mA:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: Class 3600:2011, Class 3610:2015, Class 3611:2004, Class 3810:2005,
ANSI/ISA-60079:2013, ANSI/ISA-60079-11:2014, NEMA 250:2003, ANSI/IEC 60529:2004 (R2011)
Intrinsically safe for
Class I, II, III Division 1, Groups A, B, C, D, E, F, G, T5 … T4
Class I Zone 0 AEx ia IIC T5 … T4
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G, T5 … T4
Class III, Division 1 T5 … T4
Class I Zone 2 Group IIC T5 … T4
Ambient Temperature: -40 tp 70°C for T4, -40 to 50°C for T5
Enclosure Type 4X, IP66/IP67 in accordance with only IEC 60529
Entity Parameters:
Intrinsically safe for
Supply/Output circuit: Ui30V, li=200mA, Pi=0.1W, Ci=22nF, Li=0mH
Sensor circuit: Uo=6V, lo=90=mA, Po=135mW, Co=10µF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Ui=30V, Ci=22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s., 1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
[Explosionproof approval]
Applicable standard: Class 3600, Class 3615, Class 3810, ANSI/NEMA250
Class I, Division 1, Groups A, B, C, D.;
Class II/III, Division 1, Groups E, F and G.
\’FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.\’
Enclosure Ratings: TYPE 4X
Temperature Class: T6
Ambient Temperature: -40 to 60°C (-40 to 140°F)
Electrical Connection: 1/2 NPT female(1)
 
  1. Applicable for Electrical Connection Code 2.
 
 
  • Estimated Lead Time: 6 – 8 Weeks
  • Shipping Weight: 4 Kg